Permit: T05CM03032

Parcel: 115051520


Addresses:

26 E SAHUARO ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM03032

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/18/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
*NOTE: BOND SERVICE GUTTER - WITH 3/0 COPPERS.
05/05/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. IDENTIFY PANEL DIRECTORY PROPERLY.
2. MISSING TOP STAIR 3-WAY SWITCH.
3. PROVIDE EARTH GROUND TO ALARM PANEL.
4. BLANK OFF OPEN WIRING.
5. ROLL UP DOOR NOT WORKING.
6. HAVE OBJECTIONABLE CURRENT ON BONDING CONDUCTOR GUTTER TO DISCONNECT NEC 250.06
7. SERVICE SIDE BONDING CONDUCTOR UNDERSIZED
NEC 250.66
8, IDENTIFY SERVICE DISCONNECT NEC 230