Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM03032
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/18/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* *NOTE: BOND SERVICE GUTTER - WITH 3/0 COPPERS. |
|
05/05/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. IDENTIFY PANEL DIRECTORY PROPERLY. 2. MISSING TOP STAIR 3-WAY SWITCH. 3. PROVIDE EARTH GROUND TO ALARM PANEL. 4. BLANK OFF OPEN WIRING. 5. ROLL UP DOOR NOT WORKING. 6. HAVE OBJECTIONABLE CURRENT ON BONDING CONDUCTOR GUTTER TO DISCONNECT NEC 250.06 7. SERVICE SIDE BONDING CONDUCTOR UNDERSIZED NEC 250.66 8, IDENTIFY SERVICE DISCONNECT NEC 230 |