Permit: T05CM02739

Parcel: 11306203A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
05/22/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
04/29/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/29/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. CONTRACTOR TO TAPE ABS WHERE IN CONTACT WITH NEUTRAL STUDS - OK TO COVER WALLS - 2ND FLOOR
2. WATER TEST EAST SIDE AND WEST OK (ROOF DRAINS) ADD HANGERS WHERE REQUIRED AND RECALL INSPECTION
3. CONTRACTOR MUST PROVIDE ACCURATE REDLINES ON ALL CHANGES TO THE PLUMBING SYSTEM BY NEXT INSPECTION OR YOU WILL BE CHARGED A REINSPECTION FEE
4. NEED TO SEE CLOSET FLANGES SECURED TO THE FLOOR
10/26/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PVC YARDWATER REQUIRES 12" OF COVER AT ALL POINTS
REQUIRE BLUE TRACER
2. OK TO COVER WALLS
10/23/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PLEASE CALL IN ROOF DRAIN INSPECTION WHEN THEY ARE READY. WEST SIDE ROOF DRAINS HAVEN'T BEEN INSPECTED
NO PLAN REVISION FOR COLUMN DRAINS
2. NO MORE THAN 24 DFU ON 2"
3. SUPPORTED VERTICAL PIPING
4. SUPPORT OVERHEAD PIPING

SECURE CLOSET FLANGES
10/12/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. WHO HAS BEEN INSPECTING THE ROOF DRAINS?
NOT READY FOR INSPECTION
NO TEST ON ABS
(03037 ROOF DRAINS)

NOTE: ABS IS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES THEN NO MORE THAN FOUR FEET BETWEEN HANGERS.

COPPER SUPPORTED SIMILAR
ALSO, ALL VERTICAL PIPING TO BE SUPPORTED