Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/29/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 11/29/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CONTRACTOR TO TAPE ABS WHERE IN CONTACT WITH NEUTRAL STUDS - OK TO COVER WALLS - 2ND FLOOR 2. WATER TEST EAST SIDE AND WEST OK (ROOF DRAINS) ADD HANGERS WHERE REQUIRED AND RECALL INSPECTION 3. CONTRACTOR MUST PROVIDE ACCURATE REDLINES ON ALL CHANGES TO THE PLUMBING SYSTEM BY NEXT INSPECTION OR YOU WILL BE CHARGED A REINSPECTION FEE 4. NEED TO SEE CLOSET FLANGES SECURED TO THE FLOOR |
|
| 10/26/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PVC YARDWATER REQUIRES 12" OF COVER AT ALL POINTS REQUIRE BLUE TRACER 2. OK TO COVER WALLS |
|
| 10/23/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PLEASE CALL IN ROOF DRAIN INSPECTION WHEN THEY ARE READY. WEST SIDE ROOF DRAINS HAVEN'T BEEN INSPECTED NO PLAN REVISION FOR COLUMN DRAINS 2. NO MORE THAN 24 DFU ON 2" 3. SUPPORTED VERTICAL PIPING 4. SUPPORT OVERHEAD PIPING SECURE CLOSET FLANGES |
|
| 10/12/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. WHO HAS BEEN INSPECTING THE ROOF DRAINS? NOT READY FOR INSPECTION NO TEST ON ABS (03037 ROOF DRAINS) NOTE: ABS IS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES THEN NO MORE THAN FOUR FEET BETWEEN HANGERS. COPPER SUPPORTED SIMILAR ALSO, ALL VERTICAL PIPING TO BE SUPPORTED |