Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* PLANS REVISED & STAMPED |
|
| 05/22/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PREVIOUS INSPECTION ITEMS CORRECTED 2) OUTDOOR LIGHTING NOT PER PLAN-NEED APPROVED REVISON |
|
| 05/09/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PANEL DIRECTORIES TO BE CORRECT/GO TO WHAT THEY SAY ARE GOING TO -- NEC 408.4 2. IDENTIFY ALL EQUIPMENT - NEC 110.22 3. EMERGENCY TO BE PER PLAN AND PER NEC 700.12F (LIGHTING) ON ROOF 1. SECURE ALL EQUIPMENT IN PLACE, STRAP FLEX 2. SPLIT SYSTEM FOR ELEVATOR NEEDS PROPER WIRING METHOD, SECURE IN PLACE. 3. IDENTIFY ALL EQUIPMENT PROPERLY, AND WITH METAL TAGS PARTIAL INSPECTION ONLY --- WORK IN PROGRESS |
|
| 05/08/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |