Permit: T05CM02739

Parcel: 11306203A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/16/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
PLANS REVISED & STAMPED
05/22/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PREVIOUS INSPECTION ITEMS CORRECTED
2) OUTDOOR LIGHTING NOT PER PLAN-NEED APPROVED REVISON
05/09/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PANEL DIRECTORIES TO BE CORRECT/GO TO WHAT THEY SAY ARE GOING TO -- NEC 408.4
2. IDENTIFY ALL EQUIPMENT - NEC 110.22
3. EMERGENCY TO BE PER PLAN AND PER NEC 700.12F (LIGHTING)

ON ROOF
1. SECURE ALL EQUIPMENT IN PLACE, STRAP FLEX
2. SPLIT SYSTEM FOR ELEVATOR NEEDS PROPER WIRING METHOD, SECURE IN PLACE.
3. IDENTIFY ALL EQUIPMENT PROPERLY, AND WITH METAL TAGS

PARTIAL INSPECTION ONLY --- WORK IN PROGRESS
05/08/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*