Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05CM02739

Parcel: 11306203A

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/09/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
04/08/2008 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) DO NOT ENERGIZE CIRCUITS BEFORE SAFE TO DO SO
04/03/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BONDING CONDUCTORS TO BE SIZED PER NEC 250.102C
2. BOND BUSHING MISSING SCREW - NEC 110.3 B
3. THREDLESS CONNECTORS TO BE ON PIPE, NOT THREADS
NEC 110.3B, 250.4
4. TIGHTEN ALL CONNECTIONS
5. USE W.P K.O SEALS
6. GROUNDING ELECTRODE CONDUCTOR TO CONNECT DIRECTLY TO NEUTRAL OR VIA MAIN BONDING JUMPER - 250.24
03/17/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION AT SERVICE
1. PROVIDE COMPANY LETTERHEAD FOR TORQUE LETTER
2. BOND SERVICE RISERS - NEC 250.92
3. BOND ALL SERVICE RACEWAYS AND ENCLOSURES PEN
NEC 250.92 - MYERS TYPE HUB NOT APPROVED BOND PATH
4. SHEETMETAL SCREWS NOT ALLOWED FOR GROUND CONNECTION - NEC 250.8
5. IDENTIFY ALL SERVICE DISCONNECTS - NEC 230.70(B)
6. FEEDER EQUIPMENT GROUNDS UNDERSIZED - NEC 250.122
7. REMOVE PAINT UNDER LUGS - NEC 250.12
8. NEED SEALING TYPE LOCKNUTS FOR ENTRIES ABOVE LIVE PARTS - NEC 312.2
9. PARALLEL CONDUCTORS TO BE PER NEC 310.4

PARTIAL INSPECTION - CORRECTIONS TO NUMEROUS
GO THROUGH SERVICE AND BRING TO CODE