Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 09/16/2008 | ELECTRIC - ABOVE CEILING | Approved | ||
| 03/05/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES |
|
| 02/08/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY 1. MC TO BE SECURED WITHIN 12" OF TERMINATIONS AND @ 6' INTERVALS - NEC 330.30 2. HVAC EQUIPMENT IN ATTIC TO HAVE LIGHT & RECEPTACLE NEC 210.70C, 210.63 3. PLANS SHOW HEAT STRIPS FOR FAN COILS, INTERLOCK FOR FRESH AIR & EX. FAN 4. FINISH ALL LOW VOLTAGE WIRING 5. WIRE NUTS TO BE USED AS LISTED - NEC 110.3 B 6. ALL FUSES TO BE INSTALLED 7. EMERGENCY LIGHTING TO BE PER NEC 700.12 F 8. EMT TO BE NEAT AND WORKMANLIKE, SECURED WITHIN 36" OF ENCLOSURES AT MAX. 10" INTERVALS |