Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2012 | PLUMBING - INTERMEDIATE | Approved | ||
| 10/13/2011 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ABS AND PVC TO BE SUPPORTED AT EACH CHANGE OF DIVERTION OR ELEVATION AND AT THE END OF BRANCHES THEN NO MORE THAN 4' BETWEEN HANGERS. VERTICAL PIPING REQUIRES MID STORY GUIDES 2) PLASTIC PIPE MAY NOT BE TESTED WITH AIR 3) WATER PIPE 1 1/2" AND SMALLER TO BE PEX SEE 1541D-2 PART 2 SECTION Z04B. INSTALLERS TO BE CERTIFIED SEE 302.A 4) INSULATE PER SPEC BOOK |