Permit: T05CM02434

Parcel: 137070320


Addresses:

5107 S 12TH AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/19/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
BACKFLOW PERMIT #NS3271
01/09/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE TUCSON WATER PERMIT FOR BACKFLOW INSTALLATION
2) PROVIDE CERTIFICATION FOR BACKFLOW PREVENT AFTER COMPLETING
3) REMOVE UP STREAM HOSE CONNECTION AT RP
4) SEAL WALL PENETRATIONS
5) INSTALL EXPANSION TANK BETWEEN WH AND VALVE
6) REMOVE CLEANOUT COVERS SO THAT I MAY VERIFY THE USE OF APPROVED CLEANOUT PLUGS USED TO HOLD COVER ON (DRILLING OR TAPPING ABS IS PROHIBITED)
7) ALL SINKS MUST BE WORKING FOR FINAL
8) TRAP AND TRAP ARM MUST BE THE SAME SIZE ON CAST IRON HAND SINK
9) CALL FOR MED GAS INSPECTION