Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/31/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/25/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* EXPOSE WASTE & VENT FITTINGS PROVIDE TEST THRU ROOF. |
|
| 04/12/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL PIPING TO HAVE AIR OR WATER TEST. 2. ALL OVERHEAD PIPING TO BE SUPPORTED AT CORRECT INTERVALS. PLASTIC HORIZONTAL OVERHEAD AT 4' |
|
| 04/03/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 03040 -- 2 1/2 YARD WATER FROM METER AREA TO 5' FROM COPPER STUB OUT OF BUILDING 60 PSI TEST OK ON SCH 40 PVC PIPING. 1. NEED TO SEE CONNECTION TO BUILDING AND TO METER WITH CORRECT BACKFLOW PROTECTION. 2. PROVIDE CITY APPROVED PLAN OF SHEET 2 OF 4 FOR SITE WATER AND HAVE 03040 YARD WATER INSPECTION ADDED TO PERMIT. COVER AT OWN RISK. |