Permit: T05CM02332

Parcel: 133243720


Addresses:

250 N PANTANO RD


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T05CM02332

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/31/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
05/25/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
EXPOSE WASTE & VENT FITTINGS PROVIDE TEST THRU ROOF.
04/12/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL PIPING TO HAVE AIR OR WATER TEST.
2. ALL OVERHEAD PIPING TO BE SUPPORTED AT CORRECT INTERVALS. PLASTIC HORIZONTAL OVERHEAD AT 4'
04/03/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
03040 -- 2 1/2 YARD WATER FROM METER AREA TO 5' FROM COPPER STUB OUT OF BUILDING 60 PSI TEST OK ON SCH 40 PVC PIPING.
1. NEED TO SEE CONNECTION TO BUILDING AND TO METER WITH CORRECT BACKFLOW PROTECTION.
2. PROVIDE CITY APPROVED PLAN OF SHEET 2 OF 4 FOR SITE WATER AND HAVE 03040 YARD WATER INSPECTION ADDED TO PERMIT. COVER AT OWN RISK.