Permit: T05CM02256

Parcel: 10711165B


Addresses:

3042 N BALBOA AV

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
02/14/2007 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
10/19/2006 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL ADDRESS AND UNIT NUMBERS ON SERVICE
2. IDENTIFY SERVICE DISCONNECTS.
3. TERMINATE FEEDERS AND GROUNDING CONDUCTORS.
4. BOND ANY METAL PIPING TO SERVICE -- GAS & WATER
5. INSTALL SERVICE LATERAL LUGS.
6. SEAL UNUSED OPENINGS.
7. BOND SERVICE RISER
8. STRAP SERVICE RISER
9. SERVICE RACEWAY OUT OF SERVICE INTO GROUND TO
BE 18" DEEP
10. UNITS TO BE TRIMMED OUT BEFORE POWER APPROVAL.
11. SECURE SERVICE TO STRUCTURE - GET INTO SOME STUDS AND USE BIGGER SCREWS.