Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 10/19/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. INSTALL ADDRESS AND UNIT NUMBERS ON SERVICE 2. IDENTIFY SERVICE DISCONNECTS. 3. TERMINATE FEEDERS AND GROUNDING CONDUCTORS. 4. BOND ANY METAL PIPING TO SERVICE -- GAS & WATER 5. INSTALL SERVICE LATERAL LUGS. 6. SEAL UNUSED OPENINGS. 7. BOND SERVICE RISER 8. STRAP SERVICE RISER 9. SERVICE RACEWAY OUT OF SERVICE INTO GROUND TO BE 18" DEEP 10. UNITS TO BE TRIMMED OUT BEFORE POWER APPROVAL. 11. SECURE SERVICE TO STRUCTURE - GET INTO SOME STUDS AND USE BIGGER SCREWS. |