Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* UNIT #1 - INSTALL ALL PANEL SCREWS UNIT #2 - SMOKE DETECTORS IN BEDROOMS TOO CLOSE TO WALL - CHECK INSTALLATION INSTRUCTIONS. ON THE ROOF ROOFTOP UNITS NOT PROPERLY IDENTIFIED FOR HEAT KIT AND OVERFUSED UNITS DRAIN 16.5 AMPS FULL HEAT 12 AMPS AC REFEE IF NOT CORRECT NEXT INSPECTION HAVE ALL UNITS OPEN AND LADDER FOR ROOF |
|
| 01/24/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* GO THROUGH CORRECTIONS FOR 3036 (T05CM01792) |
|
| 12/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) INSPECTION FOR SERVICE ONLY 2) IDENTIFY SERVICE DISCONNECTS-NEC 230.70(B) |
|
| 11/30/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |