Permit: T05CM02137

Parcel: 11517118A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
01/04/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
1. PLEASE PROVIDE INSPECTOR WITH APPROVAL OF 03035 INTERMEDIATE.
2. SEWER/HCS OK TO COVER
10/09/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. WATER PIPING MAY NOT PASS DIRECTLY OVER ELECTRIC SERVICE PANEL.
2. 1S-5 2003 UPC SAYS --
"...ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES. THEN, NO MORE THAN 4' BETWEEN HANGERS.
THE PROBLEM WITH YOUR UNSUPPORTED OVERHEAD HORIZONTAL PIPING -- EVEN THOUGH YOU SUPPORTED THE VERTICAL, THEN VENT CAN BE PUSHED DOWN FROM THE ROOF CAUSING BACK PITCH.
3. SECTION 301.1 2003 STATES THAT ALL PIPING, VALVES, CONNECTORS AND APPERTANCES TO BE LISTED. PLUMBERS TAPE IS NOT LISTED.
4. TRACER ON YARDWATER PIPING TO BE EXTENDED ALL THE WAY TO THE METER AND IS TO EXTEND TO 12" ABOVE GRADE AT THE HOUSE SERVICE CONNECTION.
5. IF YOU LEAVE THE PLUMBERS NAME AND PHONE NUMBER AND A REQUEST FOR 1/2 HRS. NOTICE, I CAN MEET THE PLUMBER HERE.
10/06/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. SEE 706.3 2003 UPC - CHANGES OF DIRECTION
2. SEE 704.4.3 2003 UPC - CLOSET RINGS
3. SEE IS-5 2003 UPC - 314.2 SUPPORT
4. SEE 301.1 2003 UPC STANDARDS/LISTING
5. SEE INSTALLATION STD. FOR PEX TO COPPER AT SERVICE AND WATER HEATER.
6. DO NOT INSTALL WATER PIPING OVER ELECTRIC SERVICE PANEL.
7. TRAP ARMS TO BE INSTALLED AT 1/4" PER FOOT SUPPORT TRAP ARM AS CLOSE TO THE SWEEP AS POSSIBLE.
8. TUBS NOT TESTED.
NO TEST ON ABS -- INSPECTION STOPPED NO MORE PAPER
10/02/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. YARDWATER NOT INSTALLED PER PLAN, READ PLUMBING NOTES SEE PLOT PLAN
2. INTERMEDIATE NOT INSTALLED PER PLAN, NOR TO CODE
SEE PLUMBING NOTES