Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/13/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PARTIAL OK TO START COVERING OK TO INSULATE. SEE BOBBY PAINTER ON PROTECTION OF WIRING AROUND ACCESS HOLES -- CALL ME BACK. |
|
| 10/09/2006 | ELECTRIC - INTERMEDIATE | Denied | WIRING AROUND OPENINGS TO ATTIC SUCH AS YOU HAVE HAS TO BE PROTECTED AS PER NEC 334.23 WHICH REFERS TO 320.23 IN THE NEC -- PLEASE REVIEW | |
| 10/05/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* #6 NOT DONE -- NEED TO OK WIRING AROUND FRAMING |
|
| 10/02/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. KITCHEN COUNTER CKT'S TO SERVE NO OTHER LOADS - NEC 210.52 B2 2. BATHROOM LIGHT SWITCHES BEHIND DOORS? 3. INSTALL ADDITIONAL NAIL PLATES AS NEEDED -- NEC 300.5 4. HAVE OVERFILLED BOXES IN KITCHEN, HALLWAY -- NEC 314.16, 110.3 5. EACH UNIT NEEDS ITS OWN ROOFTOP SERVICE GFI -- NEC 210.63 6. FRAME IN ATTIC ACCESS AND MAKE SURE ROMEX IS PROPERLY PROTECTED AROUND ACCESS - NEC 334.23, 320.23 SERVICE NOT COMPLETE @ THIS TIME. |