Permit: T05CM02137

Parcel: 11517118A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/23/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/13/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PARTIAL OK TO START COVERING
OK TO INSULATE.
SEE BOBBY PAINTER ON PROTECTION OF WIRING AROUND ACCESS HOLES -- CALL ME BACK.
10/09/2006 ELECTRIC - INTERMEDIATE Denied WIRING AROUND OPENINGS TO ATTIC SUCH AS YOU HAVE HAS TO BE PROTECTED AS PER NEC 334.23 WHICH REFERS TO 320.23 IN THE NEC -- PLEASE REVIEW
10/05/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
#6 NOT DONE -- NEED TO OK WIRING AROUND FRAMING
10/02/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. KITCHEN COUNTER CKT'S TO SERVE NO OTHER LOADS - NEC 210.52 B2
2. BATHROOM LIGHT SWITCHES BEHIND DOORS?
3. INSTALL ADDITIONAL NAIL PLATES AS NEEDED -- NEC 300.5
4. HAVE OVERFILLED BOXES IN KITCHEN, HALLWAY --
NEC 314.16, 110.3
5. EACH UNIT NEEDS ITS OWN ROOFTOP SERVICE GFI --
NEC 210.63
6. FRAME IN ATTIC ACCESS AND MAKE SURE ROMEX IS PROPERLY PROTECTED AROUND ACCESS - NEC 334.23, 320.23 SERVICE NOT COMPLETE @ THIS TIME.