Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T05CM02097
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/19/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 1) GAS PRESSURE TEST OK 2) GAS PIPE SIZED AT ONE INCH |
|
08/18/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) GATE LOCKED-NO ACCESS 2) PLEASE HAVE THE PLAN AND PERMIT AVAILABLE AT THE TIME OF INSPECTION |
|
08/16/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :*REMEDITION UNIT +400+000 BTU DEVELOPED LENGHT OVER 80FT 3|4IN GAS PIPE IN A DOG WET MAK ALL CONNECTIONS RUN ALL PIPE | |
08/11/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GAS PIPING TO BE SCOTCH COATED FOR UNDERGROUND USE 12" MINIMUM BURIAL DEPTH 2) GAS PIPING TO BE 6" ABOVE FINISH GRADE WHEN USING PLAIN BLACK PIPING 3) LEFT-RIGHT NIPPLE AND COUPLING SHALL BE USED WHEN UNIONS ARE NECESSARY |