Permit: T05CM02097

Parcel: 117160130


Addresses:

35 E TOOLE AV

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
08/19/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
1) GAS PRESSURE TEST OK
2) GAS PIPE SIZED AT ONE INCH
08/18/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) GATE LOCKED-NO ACCESS
2) PLEASE HAVE THE PLAN AND PERMIT AVAILABLE AT THE TIME OF INSPECTION
08/16/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*REMEDITION UNIT +400+000 BTU DEVELOPED LENGHT OVER 80FT 3|4IN GAS PIPE IN A DOG WET MAK ALL CONNECTIONS RUN ALL PIPE
08/11/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GAS PIPING TO BE SCOTCH COATED FOR UNDERGROUND USE 12" MINIMUM BURIAL DEPTH
2) GAS PIPING TO BE 6" ABOVE FINISH GRADE WHEN USING PLAIN BLACK PIPING
3) LEFT-RIGHT NIPPLE AND COUPLING SHALL BE USED WHEN UNIONS ARE NECESSARY