Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05CM01792

Parcel: 10711166A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/13/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
01/29/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
THE FITTING ON THE CONDENSATE CONNECTION NOT ALLOWED.
THE INTERAL DIAMETER IS LESS THAN 3/4"
PERMANENTLY I.D UNIT WITH THE PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY.
60 AMP FUSES MAY BE TOO LARGE.
01/23/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MARK UNIT DATA PLATE WITH THE PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. 60 AMP FUSES WILL NOT WORK WITH ANY OF THE HEATERS LISTED ON THE DATA PLATE. 60 AMP WOULD ALSO REQUIRE #6 WIRE INTO THE UNIT
2. PAINT EXPOSED PVC W/LATEX PAINT.
3. PROVIDE SCREEN IN ALL T-TOPS EXCEPT DRYER VENT.
4. CONDENSATE CONNECTION TO UNIT 2 NOT CORRECT.
5. EXTEND COVER OVER CANVAS CONNECTORS ALL THE WAY DOWN BOTH SIDES.
6. PROVIDE ACCESS INTO BLDG.