Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* ROOFTOP UNITS NOT CORRECTLY IDENTIFIED FOR HEAT STRIPS UNIT OVERFUSED. REFEE IF NOT CORRECT NEXT TIME HAVE ALL UNITS OPEN AND LADDER FOR ROOF |
|
| 01/24/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* UNIT #1 1. PROVIDE ARC FAULT PROTECTION FOR BEDROOM LIGHT NEC 210.12 B 2. INSTALL ALL LIGHT BULBS 3. CHECK ROOFTOP UNITS - IT APPEARS THAT BRANCH CKTS ARE UNDERSIZED/NOT FUSED PROPERLY. UNITS NAMEPLATES TO BE CLEARLY IDENTIFIED. UNIT #2 SAME AS UNIT #1 PLUS 1. ARC FAULT FOR SOUTH BEDROOM NOT TESTING/TRIPPING 2. HAVE SEVERAL LOOSE DEVICES - TIGHTEN AS NEEDED |
|
| 12/13/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THIS APPEARS TO BE AN UNDERGROUND FEED ONLY SERVICE - VERIFY THAT IT IS LISTED FOR OVERHEAD USE - NEC 110.3 2. MAST NOT PROPERLY BONDED -- NEC 250.90, 250.8 3. HAVE UNIT MARKED A B & 1 2? 4. IDENTIFY SERVICE DISCONNECTS - NEC 230.70 B 5. TIGHTEN SCREWS FOR BONDING JUMPER - NEC 110.3 6. WATER SPICKET IN FRONT OF SERVICE? NEC 110 NEED DEDICATED SPACE SERVICE TO GRADE |
|
| 11/30/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |