Permit: T05CM01792

Parcel: 10711166A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/14/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
ROOFTOP UNITS NOT CORRECTLY IDENTIFIED FOR HEAT STRIPS UNIT OVERFUSED.

REFEE IF NOT CORRECT NEXT TIME
HAVE ALL UNITS OPEN AND LADDER FOR ROOF
01/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
UNIT #1
1. PROVIDE ARC FAULT PROTECTION FOR BEDROOM LIGHT
NEC 210.12 B
2. INSTALL ALL LIGHT BULBS
3. CHECK ROOFTOP UNITS - IT APPEARS THAT BRANCH CKTS ARE UNDERSIZED/NOT FUSED PROPERLY. UNITS NAMEPLATES
TO BE CLEARLY IDENTIFIED.

UNIT #2
SAME AS UNIT #1 PLUS
1. ARC FAULT FOR SOUTH BEDROOM NOT TESTING/TRIPPING
2. HAVE SEVERAL LOOSE DEVICES - TIGHTEN AS NEEDED
12/13/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. THIS APPEARS TO BE AN UNDERGROUND FEED ONLY SERVICE - VERIFY THAT IT IS LISTED FOR OVERHEAD USE - NEC 110.3
2. MAST NOT PROPERLY BONDED -- NEC 250.90, 250.8
3. HAVE UNIT MARKED A B & 1 2?
4. IDENTIFY SERVICE DISCONNECTS - NEC 230.70 B
5. TIGHTEN SCREWS FOR BONDING JUMPER - NEC 110.3
6. WATER SPICKET IN FRONT OF SERVICE? NEC 110
NEED DEDICATED SPACE SERVICE TO GRADE
11/30/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*