Permit: T05CM01792

Parcel: 10711166A

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
01/09/2007 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
12/29/2006 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) THERE IS WATER GOING THRU OLD HUB HOLES INTO SERVICE. SEAL THESE OPENINGS WITH SEALING O-RING OR GASKET AROUND SCREWS TO MAKE THEM RAIN TITE
2) STILL NEED TO PAY REINSPECTION FEE
12/19/2006 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HOSE BIB STILL IN DEDICATED AREA IN FRONT OF AND BELOW SERVICE.
2. MANUFACTURER REQUIRES MYERS TYPE HUB FOR OVERHEAD FEED AND MAKE SURE MAST IS PROPERLY BONDED.

WILL NEED TO PAY REINSPECTION FEE.