Permit: T05CM01792

Parcel: 10711166A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/14/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/07/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ELECTRICAL COVER
09/06/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROPERLY GROUND ALL METAL BOXES
2. PANEL CLAMP FOR FEEDER LOOSE
3. SEAL UNUSED OPENING IN PANEL
4. HOOD NOT ALLOWED ON FRIDGE CKT NEC 210.52 B1

OK TO COVER COMMON WALL
08/30/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL PANEL FEEDER
2. KITCHEN RECEPTACLES TO HAVE NO OTHER LOADS EXCEPT AS PERMITTED BY NEC (2002) 210.52(B)
3. BATHROOM RECEPTACLE TO HAVE NO OTHER LOADS
NEC 210.11(C)(3)
4. TIGHTEN ALL METAL BOX GROUND SCREWS AND WRAP GROUND MIN. 2/3RDS AROUND GROUND SCREW - NEC 110/250
5. REMOVE BONDING STRAP IN SUB-PANEL AND GROUND SUB-PANEL ENCLOSURE - NEC 408.20
6. IDENTIFY WHITE CONDUCTOR USED AS HOT -- NEC 310.11
BOTH UNITS
08/25/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
HAVE UNIT WIRING MIXED WITH OTHER UNIT CHECK BOX SPACING (IN SAME CAVITY?) WITH BUILDING INSPECTOR.