Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/07/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ELECTRICAL COVER |
|
| 09/06/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROPERLY GROUND ALL METAL BOXES 2. PANEL CLAMP FOR FEEDER LOOSE 3. SEAL UNUSED OPENING IN PANEL 4. HOOD NOT ALLOWED ON FRIDGE CKT NEC 210.52 B1 OK TO COVER COMMON WALL |
|
| 08/30/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. INSTALL PANEL FEEDER 2. KITCHEN RECEPTACLES TO HAVE NO OTHER LOADS EXCEPT AS PERMITTED BY NEC (2002) 210.52(B) 3. BATHROOM RECEPTACLE TO HAVE NO OTHER LOADS NEC 210.11(C)(3) 4. TIGHTEN ALL METAL BOX GROUND SCREWS AND WRAP GROUND MIN. 2/3RDS AROUND GROUND SCREW - NEC 110/250 5. REMOVE BONDING STRAP IN SUB-PANEL AND GROUND SUB-PANEL ENCLOSURE - NEC 408.20 6. IDENTIFY WHITE CONDUCTOR USED AS HOT -- NEC 310.11 BOTH UNITS |
|
| 08/25/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* HAVE UNIT WIRING MIXED WITH OTHER UNIT CHECK BOX SPACING (IN SAME CAVITY?) WITH BUILDING INSPECTOR. |