Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2005 | PLUMBING - ROUGH, SOIL | Approved | DWV WATER TEST IS OK UNDERGROUND RWL WATER TEST IS OK OK TO BACKFILL TRENCH. IVRS - Inspection :* |
|
| 09/27/2005 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT BRIDGE THE SHADING FOR 6" RWL. SHALL SHADE THE ENTIRE TRENCH AND LAID ON A FIRM BED. CHECK 6" FOR PITCH 2) RWL ARE NOT INSTALLED AS PER PLAN 3) SEE NOTE #2 AND 3 AS REQUESTED 4) DO NOT COVER |
|
| 09/20/2005 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HCS CONNECTION IS OK 2) NOTE: IT APPEARS THAT THERE ARE SOME 4" STACKS MISSING AND FUTURE FLOOR DRAINS 3) APPROVED PLANS CALL FOR 4" TRAP ARMS @ WATER CLOSETS. A SEALED LETTER FROM THE ARCHITECT STATEING THAT 3" TRAP ARMS FOR WATER CLOSETS ARE ACCEPTABLE IS OK PRIOR TO FINAL |