Permit: T05CM01744

Parcel: 110103110


Addresses:

3194 N SWAN RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
10/04/2005 PLUMBING - ROUGH, SOIL Approved DWV WATER TEST IS OK
UNDERGROUND RWL WATER TEST IS OK
OK TO BACKFILL TRENCH. IVRS - Inspection :*
09/27/2005 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CANNOT BRIDGE THE SHADING FOR 6" RWL. SHALL SHADE THE ENTIRE TRENCH AND LAID ON A FIRM BED. CHECK 6" FOR PITCH
2) RWL ARE NOT INSTALLED AS PER PLAN
3) SEE NOTE #2 AND 3 AS REQUESTED
4) DO NOT COVER
09/20/2005 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HCS CONNECTION IS OK
2) NOTE: IT APPEARS THAT THERE ARE SOME 4" STACKS MISSING AND FUTURE FLOOR DRAINS
3) APPROVED PLANS CALL FOR 4" TRAP ARMS @ WATER CLOSETS. A SEALED LETTER FROM THE ARCHITECT STATEING THAT 3" TRAP ARMS FOR WATER CLOSETS ARE ACCEPTABLE IS OK PRIOR TO FINAL