Permit: T05CM01744

Parcel: 110103110


Addresses:

3194 N SWAN RD

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
06/22/2006 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
03/16/2006 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
INCOMPLETE INSPECTION
03/15/2006 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
INCOMPLETE INSPECTION
03/13/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) ELEVATOR (17' 4"-21'-4")
2) INTERIOR COLUMNS N.W. OF ELEVATOR (13' 4"-17' 4") N.W. WALLS AT CENTER PORTION OF BLDG (24'-28')
03/06/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
N.W. & S.E. WALL OF SHELL #201 AROUND CENTER STAIR AREA (17'4"-21'4") EXTERIOR WALL/AREA @ SOUTH STAIRS (26'8"-30')
02/23/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
CENTER PORTION OF SHELL #201, WALLS N.E., N.W. & S.E. OF ELEVATOR (13'4" - 17'4")
(2) EXTERIOR COLUMNS @ S-SIDE OF BUILDING (19'4"-22'4")
02/17/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EXTERIOR COLUMNS (S.COLUMNS) @ EASTSIDE OF BUILDING (18'8"-23') - EXTERIOR COLUMNS @ SOUTHSIDE OF BUILDING (15'4"-19'4")
02/15/2006 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*INCOMPLETE INSP
02/13/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
2 COLUMNS @ EAST SIDE OF BUILDING, S. COLUMNS (10'8"-14'8"), N. COLUMNS (14'8"-18'8"); 2 COLUMNS @ SOUTHSIDE OF BUILDING (10'8"-15'4")
02/10/2006 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
CONTRACTOR GROUTING ON 2/13/06 INCOMPLETE INSPECTION
02/06/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) LINES 2.3/C.?-E, E-7/23-23.3 (12'-14' 8")
02/02/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*COLUMN @ N.W SIDE OF LOBBY ( 13'4" -18')
01/31/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) ELEVATOR (8'-13' 4"); COLUMNS NORTH OF ELEVATOR (8'-12')
01/30/2006 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
01/27/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) S. W. WALL OF ROOM #102 AND CENTER STAIRS (8'-13' 4"); ELEVATOR AND 2 COLUMNS AT S.E. SIDE OF ROOF #100 (4'-8'); LINE 11/S-T (9'-4"-13' 4")
01/24/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) EXTERIOR WALL AT S.E. SIDE OF BLDG (12' 8"-14')
01/22/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
S.W. WALLS OF ROOM #102 & CENTER STAIRS (4'8"-8'8"); ELEVATOR (0-4'); N.W. COLUMNS/WALLS OF LOBBY #100 (8'8"-12'); EXTERIOR COLUMNS/WALLS @ S.E. SIDE OF BUILDING 8'8"-12'8"
01/19/2006 REINFORCED MASONRY PRE-GROUT Cancelled CANCELLED PER LAURA OF VENTURE WEST, LAURA GAVE SHERRIE AS THE PERSON TO CONTACT #465-6749
01/19/2006 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
01/17/2006 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
01/13/2006 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
01/12/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
LINES 15.5/H-L, 11/Q.S-5, 1-2/V-W, W/2-3.5 & SOUTH & STAIR AREA (8'8"-15'14")
COLUMNS @ NW SIDE OF LOBBY AND EXTERIOR COLUMNS SOUTHEAST OF LOBBY @ LINES 11-15.5/M-Q.5 (4'8"-8'8");
WALL @ LINES Q.5/8-11 (4'8"-8'8"); SW WALL OF CENTER STAIRS & ELEVATOR (0-4'8")
01/11/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) L-Q.5/11-15.5 (8'-13'4"); 15.5/H-L (4'-8')
01/06/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) LINES 1/Q-V (8'8"-13'4"), N.W. EXTERIOR COLUMNS-4 CENTER COLUMNS (0-4'8") AND 4 EXTERIOR (0-2'8")
2) CONTRACTOR TO HOLD GROUT DOWN IN ORDER TO MAINTAIN PROPER LAP SPLICES
01/04/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*WALLS/COLUMNS @ LINES 1/Q-V,2/W,11/Q-11/R ( 4'8"-8'8") COLUMNS@ LOBBY ( 0-4'8")N. WALL OF ROOM # 104 ( 8'8"-13'4) SPECIAL INSPECTOR TO VERIFY THAT GROUT IS HELD DOWN IN ORDER TO MAINTAIN PROPER LAP SPLICES
12/29/2005 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
LINES 1-5/K.5-N, 10.5-13/A-D, 1/N-Q (11' 4" - 13' 4") WALLS/COLUMNS @ LINES 11/S-V & SOUTH STAIRS (4'8" - 8'8")
12/22/2005 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) COLUMNS/WALLS AT LINES 1/Q-W, 11/Q-V AND SOUTH STAIR AREA (0-4'8")
2) CONTRACTOR WILL HOLD GROUT DOWN IN ORDER TO MOUNTAIN PROPER ? SPLICES
12/20/2005 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*LINES 10.5-13/B-D,13/A-B (4'8"-11'4") 23/B-C.5,C.5/21.5-23,22/E-L (8'8"-13'4")
12/15/2005 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) LINES L-Q/11-15.5, K-M.3/1-4, 1/M.3-Q (4'8"-9'4"); Q/8-11 (0-4'8")
12/13/2005 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) LINES A/13-15.? (4'8"-8'8"); A/15.5-23, L/15.5-22 (8'-13'4"); COLUMNS AT LINES 23/C AND 23/F (4'8"-9'4")
12/08/2005 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) S.E. WALL OF SHELL #103 (0-48")
2) WEST WALL/COLUMN OF SOUTH HALF OF SHELL #103 (OUTSIDE FACE OF POP OUT, 0-4')
12/06/2005 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*N.W WALL OF SHELL # 103 EACH SIDE OF LOBBY, W. WALL OF SHELL # 103, LINES 1/M.3-P-5 ( 0-4'8")
12/02/2005 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*EAST HALF OF SHELL # 103 NORTH WALL/COLUMNS ( 4'8"-8'8") WALLS @ STAIR AREA ( 4'8"-8'-8")
11/30/2005 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*EAST HALF OF SHELL # 103, N. WALL /COLUMNS ( 4'8" -8'8") S .WALL , LINES A/13-15.5 ( 0-4'8")
11/23/2005 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*EAST HALF OF SHELL # 103 ( 0-4'8")
11/22/2005 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*CONTRACTOR CANCELLED
09/07/2005 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) STEM WALL AT PERIMETER OK PER RFI
09/01/2005 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) YOU MAY NOT TRIPPLE SPLICE REINFORCEMENT IN MASONRY. YOU WILL NEED TO EXTEND YEAR ADDED BARS MINIMUM 32" PAST TOP OF FOOTING DOWELS