Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2006 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :* | |
| 04/12/2006 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* HCS CONNECTED TO EXISTING CLAY STUB - OK 2 SECTIONS ON SEWER HAVE LESS THAN REQUIRED SLOPE. 2 SECTIONS HAVE BACKPITCH. PROVIDE PROPER SLOPE THROUGHOUT. BUILDING DRAIN IS OK TO COVER PROVIDED THAT PROPER SLOPE CAN BE OBTAINED ON SEWER. |