Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/18/2006 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
| 09/13/2006 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1. USE PROPER LISTED RE-WASHERS FOR RISER CONDUIT KO, ALSO BOND BUSHING REQUIRED DUE TO OVERSIZED HOLE & REWASHERS. 2. PLANS CALL FOR 125AMP MAINS & COPPER WIRE. PROVIDE REVISION FOR CHANGE IN FIELD INSTALLATIONS. |
|
| 09/12/2006 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |