Permit: T05CM01624

Parcel: 11702191G

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05CM01624

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/23/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS MADE OK
2) OK FOR C OF O PENDING ANY THER INSPECTIONS, CONGRATS!
08/19/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PLEASE DON'T CALL FOR FINAL UNTIL YOU ARE READY
08/17/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) A FURNCO COUPLING IS NOT APPROVED WITHIN OR UNDER A BLDG. USE THE CORRECT FITTING I.E. MISSION STYLE COUPLING
08/15/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. CONTRACTOR CUT IN DRAINAGE FITTING FOR HAND SINK, THEN COVERED W/O INSPECTION.
08/05/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) HAND SINK MAY NOT BE INDIRECTLY WASTED
2) ICE MACHINE DRAINS NOT APPROVED
07/22/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE CORRECT BACKFLOW PROTECTION FOR ALL DIRECT CONNECTED H20 SYSTEMS THAT REQUIRE IT
2) HAVE ALL PLUMBING SYSTEMS INSTALLED
3) ALL IDIRECT DRAINAGE REQUIRES MINIMUM 1" AIR GAP AT TERMINATION INTO RECEPTOR
4) ALL DRAINS TO BE GRAVITY TO RECEPTOR
5) SUPPORT COPPER TUBING FOR H20 SUPPLY TO 3-COMP. SINK
6) PROVIDE OPEN FRONT SEATS AT STOOLS
7) FLUSH VALVE HANDLES FOR STOOLS TO BE ON WIDE SIDE OF RESTROOM
8) ONLY (1) SLIP JOINT CONNECTION SHALL BE DOWN STREAM OF P-TRAP
9) USE CORRECT LISTED GLUE FOR YOUR MATERIAL TYPE
10) THIS IS NOT A COMPLETE LIST