Permit: T05CM01332
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/27/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* / OK FINAL | |
| 05/24/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOXES MORE THAN 1/4' FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING-314.20 (METAL NOT APPROVED) 2) BOND WATER HEATER DISCONNECT ENCLOSURE 3) REJECTION PINS NEEDED AT SERVICE |
|
| 05/06/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* SERVICE UPGRADE 100 TO 150 AMP INCREASE OK TO CLEAR. CALLED TEP |