Permit: T05CM01056

Parcel: 114540630

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/16/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
(7) BACKFLOW CERTIFICATIONS TURNED IN
02/14/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SECURE EXPANSION TANK
2. PROVIDE SEPARATE DRAINAGE PER RPB TO FLOOR SINK
3. PROVIDE DRAIN FOR KEG COOLER
4. RESTROOM FLOOR DRAINS TO BE FLUSH TO FLOOR FOR NO TRIP HAZARD.
5. SECURE BACKFLOW DEVICES
6. INSTALL DRIP DRAIN FOR WATER HEATER CONDENSATE
7. PROVIDE IN HOUSE BACKFLOW CERTIFICATIONS
8. VENT FROM INTERCEPTOR TO BE LAST IRON AND TERMINATE APP 10' FROM FINISH GRADE
02/08/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
GAS CARD AT METER
02/06/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. HAVE ALL PLUMBING FIXTURES INSTALLED AND ALL EQUIPMENT REQUIRING PLUMBING CONNECTED.
2. VENT FROM WATER HEATER WHEN WITHIN 10' OF INTAKE TO BE 3' ABOVE TOP OF INTAKE WHEN WITHIN 8' OF BUILDING PARAPET TO BE 2' ABOVE