Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2006 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :* PLAN ON SITE |
|
| 11/22/2005 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :*3" GREASE WASTE INTO INTERCEPTOR WATER TEST OK 4" GREASE WASTE DISCHARGE AND 4" BUILDING SEWER WATER TEST TO POINT OF CONNECTION TO EXISTING 6" SITE SEWER 10' EAST OF MANHOLE ON SOUTH END OF BUILDING OK 2" INTERCEPTOR VENT BACK TO 2' ABOVE FINISH GRADE SOUTH EAST CORNER WATER TEST OK. NEED CITY APPROVED SITE PLAN SHOWING SEWER. COVER AT OWN RISK. |