Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/13/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/09/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. IN CANOPY'S: TIGHTEN LOOSE FITTINGS. FILL UNUSED OPENINGS (NOT EASY FITTING) SUPPORT CABLE & SEALTITE 2. CONNECT POWER TO CANOPY'S |
|
| 03/02/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK POLE LIGHT |
|
| 02/27/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*LIGHT POLE NOT BONDED 250.52 | |
| 02/17/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK CONDUIT TO POLE BASE AND POLE BASE 1. FINISH POLE LIGHT |
|
| 02/14/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*CONDUIT TO WALK IN BOX TO BE SEALED AS PER 300.7 USE AN APPROVED EXTENDER RING AT BOXES MORE THAN 1/4" FROM BOX TO SURFACE AT NON COMBUSTABLES 314.20 PROTECT CONDUCTORS FROM SHARP METAL EDGES SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 A DISCONNECTING MEANS IS NEEDED FOR ICE MACHINE CONDENSOR ON ROOF SUPPORT ANTENNA CABLE UP OFF OF ROOF AND AS PER 820.6 GROUND AS PER 820.40 SUPPORT SEALTITE OVER 4" AND TIGHTEN LOOSE FITTINGS PROTECT FROM SHARP METAL EDGES MAINTAIN WORKING CLEARANCES MASTER COOL DISCONNECT |