Permit: T05CM01056

Parcel: 114540630

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/13/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/09/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. IN CANOPY'S: TIGHTEN LOOSE FITTINGS. FILL UNUSED OPENINGS (NOT EASY FITTING) SUPPORT CABLE & SEALTITE
2. CONNECT POWER TO CANOPY'S
03/02/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK POLE LIGHT
02/27/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*LIGHT POLE NOT BONDED 250.52
02/17/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK CONDUIT TO POLE BASE AND POLE BASE
1. FINISH POLE LIGHT
02/14/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*CONDUIT TO WALK IN BOX TO BE SEALED AS PER 300.7
USE AN APPROVED EXTENDER RING AT BOXES MORE THAN 1/4" FROM BOX TO SURFACE AT NON COMBUSTABLES 314.20
PROTECT CONDUCTORS FROM SHARP METAL EDGES
SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8
A DISCONNECTING MEANS IS NEEDED FOR ICE MACHINE CONDENSOR ON ROOF
SUPPORT ANTENNA CABLE UP OFF OF ROOF AND AS PER 820.6
GROUND AS PER 820.40
SUPPORT SEALTITE OVER 4" AND TIGHTEN LOOSE FITTINGS PROTECT FROM SHARP METAL EDGES
MAINTAIN WORKING CLEARANCES MASTER COOL DISCONNECT