Permit: T05CM01056

Parcel: 114540630

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
03/13/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/25/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) TRACK LIGHTING TO HAVE SUPPORT WIRES 1 PER 4'
2) OK TO TILE EXCEPT AS NOTED
01/24/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) FIXTURES TO BE SECURELY ATTACHED TO GRID 410.16
2) SUPPORT UDV CABELING AS PER 725.6 AND 800.6