Permit: T05CM01056

Parcel: 114540630

Inspection Status: Approved

Inspection History: ROOF NAILING

Date Description Inspector Results Comments
11/15/2005 ROOF NAILING Approved IVRS - Inspection :*APPROVED
11/09/2005 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ACCESS TO ROOF, CONTRACTOR NOT ON SITE AND DOOR LOCKED
11/03/2005 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*SEE NOTE (1)
NEED MORE BLOCK TO GET TO 10' FROM EXTERIOR WALL & 4" O.C NAILING TO EXTENTS SHOWN ON PLANS
10/25/2005 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*LEDGER NAIL TO SHEAR BLOCK PER DETAIL 202
INSUFFICIENT NAILING TOP OF CRICKET DETAIL 204 INCORRECT ATTACHEMENT TO WOOD BLOCK TO ROOF ( # 10 X 3 1/2" SCREWS ASKED FOR )
PLAN CALL FOR 16D NAILS AT CONNECTIONS YOU USED 12D
SEE KEYNOTE 6 PP 53.0