Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 06/28/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT APPROVE PLUMBING FINAL UNTIL ALL OTHER INSPECTIONS HAVE BEEN APPROVED. READ INSPECTION HISTORY AND PROVIDE ITEMS REQUESTED. WATER HEATER VENT NOT INSTALLED PER DETAIL G-1 ON PLAN. PROVIDE LITERATURE FROM WH MANUFACTURER FOR VENTING REQUIREMENTS. VENT TERMINATION FITTINGS ARE NOT GLUED IN PLACE ALSO PROTECT FROM UV RAYS. PROVIDE DIELECTRIC PROTECTION FOR WATER SUPPLY TO WH. INSULATE PIPING ON ROOF PER PLAN AND TO PROTECT FROM FREEZE DAMAGE. COMPLETE INTERMEDIATE VENT PIPING ON EXTERIOR SIZE OF BLDG. PVC WATER LINE PER SPEC IS OK |
|
| 06/22/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - CALL FOR AND GET APPROVED INSPECTIONS NOT YET APPROVED BEFORE CALLING FOR FINAL INSPECTION. - WATER SHALL BE ON FOR INSPECTION. - SUPPORT GAS PIPING DROPS TO HEATERS. - PROVIDE BACKING AND SECURE MOP SINK FAUCET. - CHROME P-TRAPS NOT ALLOWED ON URINALS. - SHOWERHEAD VAC BREAKERS NOT PROPERLY INSTALLED. - PROVIDE LITERATURE FOR DIRECT VENT WH. SUPPORT PIPING AT CORRECT INTERVALS. - PROVIDE DETAIL FOR EMERGENCY SHOWERS - INSTALL DIELECTRIC. - SEAL WALL PENETRATIONS. - OVERHEAD PIPING HAS NOT BEEN INSPECTED (SHOP AREA) - REMOVE STOCK FROM MEZZ RP LOCATION. SUPPORT PIPING. - PROVIDE BACKFLOW CERT. - ON MEZZ - YOU HAVE COPPER PIPING DIRECTLY EMBEDDED IN CONCRETE. - THIS IS NOT A COMPLETE LIST OF CORRECTIONS. |