Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2006 | PLUMBING - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/05/2006 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 100 PSI TEST ON WATER PIPING CORRECT SIZE TEE INSTALLED OK REPAIR INSULATION ON HOT WATER PIPING COMPLETE INSULATION ON HW PIPING TIE WIRE STILL PRESENT. *NOTE: RADIATOR FILL HOSE REELS REQUIRE BACKFLOW PROTECTION FOR WATER SUPPLY. |
|
| 03/28/2006 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - REMOVE TIE WIRE FROM WATER PIPING. - DO NOT INSTALL A REDUCER ON A RUN, REDUCE AT TEE. - PROVIDE A FULL 3" LINE TO TEE AT 2X2X3 - BRANCH IN LOCKER ROOM - PROVIDE A MINIMUM 100 PSI TEST. - 2 1/2 HOT WATER, OK TO INSULATE. - 1 1/2 FIBERGLASS INSULATION REQUIRED ON 2 1/2" HW PIPING. |