Permit: T05CM00653

Parcel: 129043570


Addresses:

540 S NORRIS AV

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Date Description Inspector Results Comments
06/29/2006 PLUMBING - ABOVE CEILING Approved IVRS - Inspection :*
04/05/2006 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
100 PSI TEST ON WATER PIPING
CORRECT SIZE TEE INSTALLED OK
REPAIR INSULATION ON HOT WATER PIPING
COMPLETE INSULATION ON HW PIPING
TIE WIRE STILL PRESENT.
*NOTE: RADIATOR FILL HOSE REELS REQUIRE BACKFLOW PROTECTION FOR WATER SUPPLY.
03/28/2006 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
- REMOVE TIE WIRE FROM WATER PIPING.
- DO NOT INSTALL A REDUCER ON A RUN, REDUCE AT TEE.
- PROVIDE A FULL 3" LINE TO TEE AT 2X2X3
- BRANCH IN LOCKER ROOM
- PROVIDE A MINIMUM 100 PSI TEST.
- 2 1/2 HOT WATER, OK TO INSULATE.
- 1 1/2 FIBERGLASS INSULATION REQUIRED ON 2 1/2" HW PIPING.