Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/26/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SUPPORT EXTERIOR F5 2) PROVIDE COVER TO KEEP RAINWATER OUT OF SANITARY SYSTEM 3) SUPPORT COOLER DRAIN LINES 4) SUPPORT VENT ON WALL, TERMINATE VENT ABOVE WALL 5) INSULATE COPPER 6) INSTALL UNION ON WATER SUPPLY TO AIR HANDLER 7) REMOVE SHARP EDGES FROM UNISTRUT |
|
| 03/08/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SHOWER DRAINS INSTALLED OK SEWER TILE OK INTERCEPTOR VENT OK |
|
| 02/10/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 50 PSI TEST ON WATER PIPING OVERHEAD WATER PIPING FROM TOILET RMS TO WATER HEATER LOCATION OK TO COVER. HOT WATER AND HWR PIPING INSULATED WITH 1" FIBERGLASS OK |
|
| 02/07/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) DWV TEST ON MENS AND WOMENS TOILET ROOMS. LOUNGE AND MOP SINK AREAS OK. PROVIDE PLUGS IN TEST TEES 2) WATER TEST NOT HOLDING-PROVIDE TEST ON WATER 3) PROVIDE PIPING INSULATION 4) SHOWER DRAINS AND CLOSET FLANGES NOT YET INSTALLED |
|
| 02/06/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* PIPING NOT YET UNDER TEST, PROVIDED THAT TEST HOLDS OK TO INSULATE HOT PIPING RECALL FOR INSPECTION TO VERIFY WATER & DWV TEST |
|
| 02/02/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |