Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/18/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 08/17/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRIC JUNCTION BOXES MUST BE ACCESSIBLE |
|
| 08/16/2005 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* 1) NON METALLIC SHEATHED CABLE MUST HAVE SHEATHING ENTER ELECTRIC BOX BY AT LEAST 1/4" 2) METAL FASTENERS CANNOT BE USED TO SECURE ELECTRIC BOX FROM INSIDE IN THE OUTER 2/3 OF BOX |
|
| 08/15/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FURNACE GAS LINE NOT CONNECTED 2) NO INSULATION UNDER FURNACE PLATFORM 3) IMPORPERLY SPLICED ELECTRIC UNDER FURNACE 4) ALL ELETRIC SPLICES REQUIRED TO BE IN APPROVED ELECTRIC BOXES |
|
| 08/12/2005 | BUILDING - FINAL | Cancelled | CANCELLED PER JERRY OF K.B. HOMES #907-6025 | |
| 08/12/2005 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* |