Inspection History Details
Permit: T05CM00571
Inspection Status: Approved
Inspection History: ELECTRIC - OUTDOOR LIGHTING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/04/2006 | ELECTRIC - OUTDOOR LIGHTING | Approved | IVRS - Inspection :* | |
| 12/14/2005 | ELECTRIC - OUTDOOR LIGHTING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTA HOT NOT LISTED AS A CORD & PLUG APPLIANCE 2. LABEL DISCONNECT & PANEL ON OUTSIDE COVER AND MAIN DISCONNECT AS PER NOTE 12 OF PLANS. 3. TIGHTEN LOOSE BUSHING & LUG 4. SPLIT BOLT ONLY LISTED FOR 2 CONDUCTORS - A RUN & A TAP 5. GROUNDING ELECTRODE TO BE CONNECTED AT GROUNDED CONNECTION ALSO AT 1ST DISCONNECTING MEANS. 6. WHERE IS GROUND RODS AND LETTER FROM ENGINEER FOR GROUNDING CHANGE? 7. REVISE PLANS FOR TRANSFORMER MOUNTING 8. MAIN BONDING JUMPER TO BE SIZED PER 250.66 9. BLUE WIRE NUT NOT LISTED FOR THAT MANY CONDUCTORS 10. VERIFY DERATING PER 310.15 - NOTE 7 DOES NOT ALLOW COMBINING OF HOME RUNS. 11. PLEASE VERIFY WEATHERPROOFING OF SPLICES 12. WHERE ARE OUTSIDE WALL LIGHTS. 13. PLEASE OPEN FRONT LIGHTS TO VERIFY AS PER PLANS. |