Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2006 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 05/02/2006 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* THE PLASTIC BAG W/DUCT TAPE IS NOT HOLDING A WATER TEST. WATER IS BELOW STEM WALL. ALL PIPING REQUIRES 2% SLOPE (1/4" PER FOOT) 3/4 MINVS IS THE STANDARD FOR FILL. |
|
| 05/01/2006 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* DWV PIPING IS REQUIRED TO BE TESTED W/A 10' HEAD OR EQUIVALENT AIR TEST OF 5 PSI ALL PIPING SHALL HAVE 2% SLOPE MINIMUM. ALL PIPING TO BE SHADED AND COVERED W/CLEAN FILL WHICH CONTAINS NO STONES OR CHUNKS LARGER THAN 3/4" |
|
| 04/25/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* PROVIDE 1. TEST ON DWV 2. 1/4" PER FOOT SLOPE |