Permit: T05CM00552

Parcel: 132166100


Addresses:

4563 S PARK AV

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
05/03/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
05/02/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
THE PLASTIC BAG W/DUCT TAPE IS NOT HOLDING A WATER TEST. WATER IS BELOW STEM WALL.
ALL PIPING REQUIRES 2% SLOPE (1/4" PER FOOT)
3/4 MINVS IS THE STANDARD FOR FILL.
05/01/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
DWV PIPING IS REQUIRED TO BE TESTED W/A 10' HEAD OR EQUIVALENT AIR
TEST OF 5 PSI
ALL PIPING SHALL HAVE 2% SLOPE MINIMUM.
ALL PIPING TO BE SHADED AND COVERED W/CLEAN FILL WHICH CONTAINS NO STONES OR CHUNKS LARGER THAN 3/4"
04/25/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
PROVIDE
1. TEST ON DWV
2. 1/4" PER FOOT SLOPE