Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 10/25/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*VENT ON CONDENSATE DRAIN MUST BE DOWNSTREAM OF THE TRAP. MARK THE DATA PLATE ON THE FAN COIL W/PROPER HEATE STRIP INSTALLED & FUSE ACCORDINGLY. DISCONNECT HAS 50 AMP FUSES # 10 WIRE NOT ADEQUATE. DO NOT USE WHITE WIRE IN THE DISCONNECTS OUTSIDE. TAPE BOTH ENDS WITH BLACK TAPE. 30 AMP FUSES TOO LARGE FOR CONDENSORS. 25 AMP IS MAX. SEAL AROUND REFER LINE SLEEVES THRU OUTSIDE WALL. |