Permit: T05CM00490

Parcel: 13815020G


Addresses:

110 W ARAGON RD #01

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/01/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/25/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*VENT ON CONDENSATE DRAIN MUST BE DOWNSTREAM OF THE TRAP.
MARK THE DATA PLATE ON THE FAN COIL W/PROPER HEATE STRIP INSTALLED & FUSE ACCORDINGLY. DISCONNECT HAS 50 AMP FUSES # 10 WIRE NOT ADEQUATE. DO NOT USE WHITE WIRE IN THE DISCONNECTS OUTSIDE. TAPE BOTH ENDS WITH BLACK TAPE. 30 AMP FUSES TOO LARGE FOR CONDENSORS. 25 AMP IS MAX. SEAL AROUND REFER LINE SLEEVES THRU OUTSIDE WALL.