Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T05CM00254
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/15/2005 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
06/09/2005 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1. EXISTING 112 1/2 KVA TRANSFORMER CANNOT BE INSTALLED IN AN ABOVE SUSPENDED CEILING-NOW THAT TILE IS TO BE ADDED TO SUSPENDED CEILING IT WILL CLOSE OF AREA. SEC 450 OF 2002 NEC ONLY ALLOWS 50 KVA OR LESS ABOVE CEILING. 2. ONCE BREAKERS INSTALLED & TERMINATED AND BOND POSTED WILL RELEASE POWER. | |
06/06/2005 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1. PARTIAL, INTERMEDIATE OK FOR SELF STANDING DIAGONAL WALL. OK TO COVER WALL. 2. ABOVE CEILING FOR DIAGONAL WALL, HAIR COLOR & SHAMPOO OK. 3. ABOVE CEILING FOR SKIN CARE & SALON AREAS OK TO COVE. 4. FLOOR BOXES ( FOUR) INSTALLED OK TO COVER. | |
06/01/2005 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* OK HARD CEILING SALES AREA. OK COLUMNS. OK OFFICE & STORAGE WALLS. |