Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T05CM00254

Parcel: 12801005H

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05CM00254

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/28/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/06/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/01/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/31/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*FINISH WIRING CANS. OK BACK WALL OF OFFICE
05/26/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FILL UNUSED OPENINGS IN BOXES
2) FINISH #1, 2, 3 AND 5 PREVIOUS INSPECTION
3) OK COLUMN 3 SIDES-ROOMS 107, 109, 110, 102, 101 AND 104
05/24/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) SUPPORT M/C CABLES WITHIN 12" OF BOXES
2) TIGHTEN LOOSE FITTINGS
3) INSTALL PLASTER RINGS
4) PREVENT DIE-ELECTRIC CONTACT
5) ALL JUNCTION BOXES TO BE ACCESSIBLE
05/23/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :* / CANCELLED BY OFFICE.