Permit: T05CM00051

Parcel: 11507094E


Addresses:

311 W ELM ST #1101

Inspection Status: Cancelled

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
08/18/2006 PLUMBING - INTERMEDIATE Cancelled IVRS - AP canceled
08/16/2006 PLUMBING - INTERMEDIATE Cancelled IVRS - AP canceled
07/11/2006 PLUMBING - INTERMEDIATE Not ready for Inspection WHO GAVE PERMISSION TO COVER WALLS AND CEILINGS?
NO PORTION OF ANY WORK MAY BE CONCEALED UNTIL IT HAS BEEN INSPECTED AND APPROVED. THIS INCLUDES DRYWALL AND INSULATION.
07/10/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
OK TO COVER ALL AREAS
CLOSET FLANGES OK
06/30/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NEED TO SEE 1ST FLOOR CLOSET FLANGES SECURED
2) FHA STRAPS AS REQUIRED
3) OK TO COVER WALLS
06/29/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
06/26/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. NO AVB'S
- NO TEST ON ABS
- PLEASE MAKE ALL CORRECTIONS BEFORE RECALLING INSPECTION.
- PLEASE POST YOUR ADDRESS
- INSPECTION STOPPED.
06/22/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
UNABLE TO LOCATE PLANS.
1. WATER USED DURING CONSTRUCTION SHALL BE PROTECTED BY A VACUUM BREAKER.
2. NOT UNDER TEST - DWV
3. TUBS NOT FULL
4. CLOSET FLANGES NOT SECURED TO FLOOR.
5. SWEEPS REQUIRED.
6. 18" OF COPPER TUBE BETWEEN PEX AND SOLDER VALVES (WATER SERVICE).
7. TRAP ARMS REQUIRE 1/4" PER SLOPE
8. WH DRAIN PANS REQUIRES ON SUBFLOOR.
9. SHOWER HEAD RISERS NOT UNDER TEST.
10. 2ND STORY SINKS AND WASHER BOXES REQUIRE CLEAN OUTS FOR HORIZONTAL PIPING BELOW SLAB PER TUCSON CODE AMENDMENTS.