Permit: T05CM00051

Parcel: 11507094E


Addresses:

311 W ELM ST #1101

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/30/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/29/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
HAVE DOORS UNLOCKED FOR INSPECTION
NO RESPONSE TO 1/2 HR CALL/PAGE
08/28/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MAKE SURE ALL ARC FAULT BREAKERS ARE WORKING
2. MAKE SURE ALL GFI'S ARE WORKING
GO THROUGH ALL INSTALLATION
08/24/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CHECK KITCHEN COUNTER RECEPT INSTALLATION FOR PROPER PLACEMENT.
08/21/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. ARC FAULT BREAKERS NOT WORKING
2. BATH GFCI NOT WORKING
3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE ATI NON-COMBUSTIBLES TO USE AN APPROVED EXTENDER RING.
4. LABEL PANELS
5. SECURE NM CABLE TO DISCONNECTS
6. SHEATHING TO EXTEND 1/4" INTO DISCONNECTS
7. TIGHTEN LOOSE FITTING WATER HEATER
8. CLEAR EXCESS DIRT FROM BOTTOM OF PANEL 110.12
9. USE CORRECT AMPACITY OF CONDUCTOR FOR NM CABLE 330.80
10. LIGHT FIXTURE TO COVER BOX
11. PLEASE VERIFY SMOKE DETECTORS ON ARC FAULT CIRCUIT