Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/29/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* HAVE DOORS UNLOCKED FOR INSPECTION NO RESPONSE TO 1/2 HR CALL/PAGE |
|
| 08/28/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MAKE SURE ALL ARC FAULT BREAKERS ARE WORKING 2. MAKE SURE ALL GFI'S ARE WORKING GO THROUGH ALL INSTALLATION |
|
| 08/24/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CHECK KITCHEN COUNTER RECEPT INSTALLATION FOR PROPER PLACEMENT. |
|
| 08/21/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. ARC FAULT BREAKERS NOT WORKING 2. BATH GFCI NOT WORKING 3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE ATI NON-COMBUSTIBLES TO USE AN APPROVED EXTENDER RING. 4. LABEL PANELS 5. SECURE NM CABLE TO DISCONNECTS 6. SHEATHING TO EXTEND 1/4" INTO DISCONNECTS 7. TIGHTEN LOOSE FITTING WATER HEATER 8. CLEAR EXCESS DIRT FROM BOTTOM OF PANEL 110.12 9. USE CORRECT AMPACITY OF CONDUCTOR FOR NM CABLE 330.80 10. LIGHT FIXTURE TO COVER BOX 11. PLEASE VERIFY SMOKE DETECTORS ON ARC FAULT CIRCUIT |