Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* 1) DO NOT ENERGIZE ANY CKT'S UNTILL ALL IS TRIMMED AND SAFED OFF |
|
| 06/30/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NEED RECEPTACLE WITHIN 6' OF BROKEN WALL LINE IN 3 BEDROOMS - HAVE NICK IN 12/2 ROOF STUB UP OK ELECTRICAL 2ND LEVEL COVER AFTER CORRECTIONS. |
|
| 06/27/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO COVER ELECTRICAL IN LOWER LEVEL ONLY |
|
| 06/21/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. INSTALL OUTLETS (RECEPTACLES) WITHIN 6' OF BROKEN WALL LINE AND NO MORE THAN 12' BETWEEN OUTLETS - NEC 210.52 2. TIGHTEN GROUND SCREWS ON METAL BOXES - NEC 110.14 3. SECURE AND SUPPORT ROMEX (AND TERMINATE) AS REQUIRED NEC 334.30 4. SECURE AND SUPPORT LOW VOLTAGE WIRING - NEC 314.16 5. YOU HAVE OVERFILLED BOXES - CHECK BOX FILL - NEC 314.16 2ND LEVEL NOT ROUGHED AT THIS TIME. |