Permit: T05CM00051

Parcel: 11507094E


Addresses:

311 W ELM ST #1101

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/07/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
1) DO NOT ENERGIZE ANY CKT'S UNTILL ALL IS TRIMMED AND SAFED OFF
06/30/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
NEED RECEPTACLE WITHIN 6' OF BROKEN WALL LINE IN 3 BEDROOMS - HAVE NICK IN 12/2 ROOF STUB UP
OK ELECTRICAL 2ND LEVEL COVER AFTER CORRECTIONS.
06/27/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO COVER ELECTRICAL IN LOWER LEVEL ONLY
06/21/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL OUTLETS (RECEPTACLES) WITHIN 6' OF BROKEN WALL LINE AND NO MORE THAN 12' BETWEEN OUTLETS -
NEC 210.52
2. TIGHTEN GROUND SCREWS ON METAL BOXES - NEC 110.14
3. SECURE AND SUPPORT ROMEX (AND TERMINATE) AS REQUIRED NEC 334.30
4. SECURE AND SUPPORT LOW VOLTAGE WIRING - NEC 314.16
5. YOU HAVE OVERFILLED BOXES - CHECK BOX FILL -
NEC 314.16
2ND LEVEL NOT ROUGHED AT THIS TIME.