Permit: T05BU02807

Parcel: 133250750


Addresses:

8642 E COLETTE ST

Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Date Description Inspector Results Comments
04/25/2006 POOL/SPA ELECTRIC Approved IVRS - Inspection :*
04/19/2006 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MUST USE COMMON TRIP 220 BREAKER FOR POOL PUMP.
SEE PRIOR WRITE UP ON 1/4/06
2. INSTALL SVRS
3. T/P VALVE MUST AIM DOWN TOWARD GROUND
01/04/2006 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1) A 220 BREAKER MUST HAVE BOTH LEGS TIED TOGETHER FOR A COMMON TRIP
12/30/2005 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LIGHT NOT BONDED
2) WIRES NOT CONNECTED AT PANEL
3) WHEN ENTERING TOP OF PANEL A ? HUB IS REQUIRED
4) GAS NOT BONDED
5) T/P VALVE REQUIRED