Permit: T05BU01446

Parcel: 110060760

Inspection Status: Approved

Inspection History: GRADING - FINAL

Date Description Inspector Results Comments
02/12/2008 GRADING - FINAL Approved INSPECTED TO THE AS-BUILT PLANS IN THE INSPECTION FILE
09/20/2007 GRADING - FINAL Denied SITE SUPERINTENDENT DAVID STEWART - 235-9077
GRADING PERMIT IS EXPIRED AND MUST BE RE-NEWED.
BUILDING FFE HAS BEEN RAISED APPROXIMATELY 1' ABOVE APPROVED PLAN FFE.
GRADING PLAN IS EXPIRED. IT WAS DESIGNED BY NORMAN AMY, AND REVIEW BY PATRICIA GILBERT FOR THE C.O.T.
THE GRADING PLAN APPEARS TO REQUIRE REVISIONS TO INCLUDE ADDITIONAL INFORMATION.

THE RETENTION/DETENTION BASIN WILL BE DEEPER THAN 2' AND WILL REQUIRE BARRICADE RAILING AND MORE ROCK RIPRAP FOR STEEP SLOPES,

SITE RECEIVES OFF-SITE RUN-ON Q100 7.3 CFS AND DISCHARGES Q100 7.0 CFS. THERE IS OUTFALL OR WALL OPENING PROVISIONS OR DETAILS FOR THE DISCHARGE FROM THE R/D BASIN.

A 2' BENCH AT EXISTING GRADE IS REQUIRED AT THE INSIDE PERIMETER OF THIS SITE. THE GRADING PLAN SHOULD SHOW THIS BENCH AS WELL AS THE SLOPES AND DEPTH OF THE SWALE.
09/19/2007 GRADING - FINAL Denied 1. GRADING AND ENGINEERING INSPECTIONS WILL BE PERFORMED USING ONLY THE APPROVED GRADING AND SITE PLANS.
2. CONSTRUCT TO THE APPROVED PLANS OR PROVIDE REVISED PLANS TO SHOW ALL MODIFICATIONS.
SEE GENERAL NOTE #11 ON THE GRADING PLAN PAGE G.1.