Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T04PL01956
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/12/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :*/1)CORRECTIONS MADE OK 2)OK FOR GAS 3)UCC LEFT AT METER SET | |
11/05/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/YOU CANNOT USE PVC COLD WATER PIPE ON A T&P DRAIN. MUST BE CPVC, COPPER, GALVANIZED. PROVIDE 3 SCREWS IN EACH JOINT OF VENT ON WATER HEATER |
|
11/03/2004 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/11 PSI TEST IS OK. FINISH HOOKING UP WATER HEATER. MUST HAVE DOUBLE WALL VENT PIPE THRU THE ROOF WITH MIN. 1" CLEARANCE FROM THE WOOD IN THE CEILING. CONNECT THE WATER PIPES & INSTALL A TEMPERATURE & PRESSURE RELIEF VALVE DRAINED TO THE OUTSIDE. NEED TO SEE GAS APPLIANCES INSIDE HOME. BE SURE ALL GAS SHUT OFF VALVES ARE AGA OR CSA APPROVED VALVES. RESCHEDULE AN INSPECTION AFTER CORRECTIONS HAVE BEEN MADE & SOMEONE WILL BE HOME. |