Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T04PL01775
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2004 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :*/12PSI TEST IS OK. ALL CORRECTIONS HAVE BEEN MADE. | |
09/29/2004 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)PROVIDE AGA OR CSA APPROVED GAS VALVES FOR ALL APPLIANCES. 2)VENT FROM WATER HEATER & FURANCE WHEN WITHIN 10' OF COOLER INTAKE TO BE 3' ABOVE TOP OF COOLER INTAKE. 3)WATER HEATER T&P DRAIN TO GRAVITY DRAIN TO DAYLIGHT. 4)SECURE ALL PIPING PROPERLY 5)PROVIDE LOWER COMBUSTION AIR INTAKE FOR WATER HEATER CLOSET. 6)PROVIDE BONDING OF BUILDING GAS PIPING |