Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/19/2004 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) REMOVE THE THREAD PROTECTOR YOU INSTALLED AT THE MAKE UP NIPPLE AND COUPLING AND USE AN APPROVED COUPLING. REMOVE THE EXISTING UNION AT EAST END OF PIPE AND USE A REVERSE THREAD COUPLING AND NIPPLE 2) IF YOU ARE NOT GOING TO CONNECT THE OTHER FURNACE ON THIS GAS LINE, REMOVE THE TEE THAT IS SUPPLYING THE ABANDONED UNIT. OTHERWISE THE 1" GAS PIPE IS NOT ADEQUATE FOR BOTH UNITS. PLEASE PROVIDE SIZING, IT IS NOT ADEQUATE FOR BOTH UNITS. PLEASE PROVIDE SIZING PLAN 3) SYSTEM IS NOT HOLDING PRESSURE. MAKE NECESSARY REPAIRS AND RETEST SYSTEM. NOTE: ALL COUPLINGS ON EXISTING PIPE ARE THREAD PROTECTORS AND MAY LEAK |