Permit: T04ME00493

Parcel: 114471390


Addresses:

2938 N RIO VERDE DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/12/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*CORRECTIONS HAVE BEEN MADE
01/04/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :* 1) PANEL COVER INSIDE SWITCH, NOT SCREWED. 2) GAS LINE NOT SUPPORTED AT CHANGE OF DIRECTION. COMPLETE RECALL FOR FINAL CORRECTION.
10/28/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)#8 WIRE NOT ADEQUATE FOR 60 AMP CIRCUIT FROM DISCONNECT TO A/C UNIT. PROVIDE A SCREW ON THE COVER PLATE INSIDE DISCONNECT. 2)GAS SHUT OFF VALVE MUST BE NSTALLED BEFORE THE FLEX CONNECTOR. SUPPORT GAS LINE AT ELBOWS. 3)CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. IF TERMINATING TO THE GROUND, DIRECT THE WATER AWAY FROM THE FOUNDATION. RECALL FOR INSPECTION