Case: T04FR00802

Parcel: 11711080B


Addresses:

125 E PENNINGTON ST

Inspection Status: Approved

Inspection History: COMPL - REINSPECTION

Date Description Inspector Results Comments
04/05/2006 COMPL - REINSPECTION Approved on this date sprinkler 2006 inspection completed and Fire final for C of O was approved
07/14/2005 COMPL - REINSPECTION Violation certificate of Occupancy still needed.
07/14/2005 COMPL - REINSPECTION Approved approved on 1-5 of civil citations
04/15/2005 COMPL - REINSPECTION Partial Approval Citations issued for the following on 2nd reinspection:
1). Failure to repair fire alarm system-TFC 906.1
Currently fire alarm system has not been repaired. Currently pull stations are activated, and trouble lights are present. (Photo).

2). Failure to remove foam from walls. TFC 806.1
Currently, carpet type cellular foam is permanently affixed to the walls of each of the 72 rooms. The foam is covering more than 10 percent of the wall, and is not being used as trim. (Photo)

3). Failure to remove unauthorized wall coverings (felt type textile) from wall that does not meet required criteria (Table 806.3). TFC 806.3
The flame spread rating for this material has not been supplied to the Tucson Fire Department as requested on 2 occasions. This material is in all 72 rooms. (Photo)

4). Failure to remove unauthorized locks from doors to practice rooms. -TFC 1008.1.8.4
Flush bolts are being used on the entrance side of each door. In addition, flush bolts are padlocked, on the entrance side. There are 2 of these locks on each of the 72 doors. (Photo)

5) Failure to provide key box for access. -506.1
A key box is required because access in this building would be extremely difficult due to metal door will keypad access, and no other immediate access to stairwell. Manager of building Mr. Burnham, has been notified of the process to obtain key box.

6). Failure to comply with Tucson Fire Department written order to obtain a Certificate of Occupancy. TFC 109.2.2
On 2 occasions, a written order, by certified mail, was given to Francisco Studios to obtain a Certificate of Occupancy. Application was mailed to Francisco Studios with the original report. Non-compliance as of this date.