Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - HIGH PILED COMBUSTIBLES
Case Number - T04FR00726
Inspection Description - VIOL - HIGH PILED COMBUSTIBLES
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/03/2004 | VIOL - HIGH PILED COMBUSTIBLES | Correction Required | 2305.4 Aisle maintenance - When restocking is not being conducted aisles shall be kept clear. When restocking manually 24 inches shall be maintained for aisles less than 48 inches wide, or one-half aisle width for aisles over 48 inches wide. |