Case Number: T04FR00726
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
12/03/2004 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 A working space of 36 inches in depth and the width of the equipment shall be maintained in front of electrical service panels.
12/03/2004 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 906.7 The portable fire extinguisher in the stockroom shall be mounted.
12/03/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 Exit signs throughout shall be illuminated at all times.
12/03/2004 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.5 Emergency illumination light in breakroom shall be repaired.
12/03/2004 VIOL - HIGH PILED COMBUSTIBLES TKNAPP Correction Required 2305.4 Aisle maintenance - When restocking is not being conducted aisles shall be kept clear. When restocking manually 24 inches shall be maintained for aisles less than 48 inches wide, or one-half aisle width for aisles over 48 inches wide.

Completed Inspections

Case Status: COMPLETE
Case Number: T04FR00726
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/11/2005 INSP - FULL TKNAPP Approved