Case: T04FR00723

Parcel: 13613001M

Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
12/02/2004 VIOL - BUILDING SVCS & SYSTEMS Violation tfc 605.3- Working space and clearance. A working space of not less than 30" in width, 36" in depth, 78" in height shall be provided in front of electrical service equipment.
12/02/2004 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.6- Unapproved conditions. Open junction boxes and open wiring splices shall be prohibited. (above parts room)